![]() |
|
INTRODUCTION This paper primarily addresses the location
of the measurement of oxygen in flue gas depending on the type of boiler
and if it is a balanced draft type or pressure furnace. Boilers which
have negative pressures in the back passes of the boiler or with penthouses
operating at a positive pressure referenced to furnace pressure will
have entrained air in the flue gases exiting the economizer. This entrained
or tramp air becomes significant when low excess air operation is done.
An approach using high temperature oxygen probes measures the oxygen
content in most cases prior to the air entrainment. OXYGEN MEASUREMENT Zirconium Oxide based oxygen analyzers
are the latest ma or development in measuring oxygen in flue gas. Zirconium
oxide is a ceramic that will allow the transfer of oxygen ions across
its matrix at temperatures above 650 degrees Centigrade (1200 degrees
Fahrenheit). This transfer of ions and the subsequent electrical charge
buildup is proportional to an oxygen differential across the Zirconia
cell.
There are three types of Zirconia based
analyzers: A) Heated in-situ (used in temperatures
of less than 1200 degrees Fahrenheit) B) Extractive and close coupled extractive
C) In-situ high temperature Zirconia must be at 1200 degrees Fahrenheit or higher to respond to the presence of oxygen. There are two popular ways of maintaining
the Zirconia cell at 1200 degrees or greater. 1. Use an auxiliary heater in close proximity
to the cell along with a control loop to regulate the power flow for
the heater. This method assumes a constant temperature and measures
the millivolt output of the cell which is inversely proportional to
oxygen. This type is used in both in-situ and close coupled extractive
types. 2. The high temperature Zirconia probe uses the process as its heat source. In this case both the temperature and the millivolt output
of the Zirconium Oxide cell are measured and applied to the Nernst equation. E = .0215 x T x Ln ( O2 Reference/02
Furnace ) Where E = Sensor output in millivolts T = Sensor temperature in degrees Kelvin 02 Reference = Oxygen concentration on inside surface of the sensor ambient air: 20.9 % oxygen 02 Furnace = Oxygen concentration in
furnace atmosphere
The heated in-situ and extractive types
are typically mounted in the back pass of a boiler. There are many installations
using this type of sensor. There are often problems with the extractive
types because of sample system maintenance. The heated in-situ designs
do not have as many sampling problems but there are maintenance requirements
that in many cases become intense. The maintenance requirements will
vary with the fuel burned, with gas requiring the least maintenance.
Oil and coal provide increasing problems due to heavier particulate
and contaminate inclusions. These are typical maintenance problems and
they are dealt with as routine. The more serious problem with these
analyzers is not maintenance, accuracy of the device or durability,
it is the location in which they are used. The back pass or economizer outlet installations
are subject to the influence of air infiltration anywhere between the
burner zone and point of measurement. The effect becomes exaggerated
if there is a pressurized penthouse. Leakage may become more severe
as the unit ages. Installation of high temperature sensors in various
locations in the radiant section of the boiler minimizes the effect
of this "tramp' air. This provides a far more representative reading
of the actual boiler combustion conditions than back pass measurements.
The high temperature sensor also requires far less maintenance than
the other types because it does not use any heaters or sample systems.
The sensors may be mounted through existing doors or ports but if there
is not a satisfactory existing location, waterwall tubes may have to
be bent during an outage to provide n opening into the upper furnace
area. Boilers which were built prior to the late 70's have burner and windbox arrangements which were designed to have excess air of 10% or greater. Distribution between burners generally is unequal. Proponents of CO control generally show a text book version of the 02 versus CO curve and recommend that the optimum point to operate is in the 02/CO knee. In actual application, the knee varies considerably.
Some of the factors are:
1. Erratic signal of CO measurement of
200 to 400 PPM on a 0-1000 PPM scale. 2. The fuel/air ratio curve on a per
burner basis is very different and non-linear with load. 3. Lack of stability or positioning ability
of both fuel and air control actuators. 4. Air in-leakage from pressurized penthouses. This leakage varies with (A) size of the leak, (B) unit load, or (C) differential pressure between the penthouse and the furnace. 5. Horizontal and vertical stratification
in the duct where the conventional 02 measurement is made. 6. Most curves given in previous papers
showing the knee (crossover point) of 02/CO are based on 02 readings
taken at the economizer outlet. These measurements include any entrainment
air (tramp air) and, therefore, do not accurately represent the 02 of
the combustion gases in the furnace. CO measurement is normally only Applicable
at loads above 70% of full load, therefore, a reliable 02 measurement
is essential for set point control at loads below 70%. A high temperature
02 probe in the furnace is a new application of a proven probe in the
steel and glass industry. It offers a lot of possibilities and solutions
to some of the problems listed above.
At GSU the first installation was two
probes in the front wall across from the archway on a supercritical
unit. As the unit picked up load above 75 %, the 02 was being controlled
at 2.8% at the economizer outlet. The two furnace probes indicated 0%
and 1.2%. This generally indicated a difference between furnace 02 and
economizer outlet 02 as much as 2 %. Further tests revealed that the difference
in 02 between the two measurement points was directly affected by the
penthouse to furnace differential pressure (DP). The DP is normally
held between 0.5 inches H20 and 1.0 inch H20. This DP control is frequently
inadequate on many boilers, therefore, the error of 02 becomes a function
of leakage area and DP.
A later installation with four probes gave a better understanding of the difference of 02 from side to side. It was found that in each case when a large difference between sides was seen, it was a result of a bad operating burner or air register. Operating with these high temperature probes in place revealed the following interesting bits. of information: 1. Different burners in service could
change the 02 reading between sides as much as 2% 02 at loads where
burners could be removed. This proved that the air distribution to the
individual burners was inadequate and air register adjustments were
required. 2. The probes also have a temperature
measurement, and at approximately the same load during the daily load
cycle, a temperature difference of 40 degrees Fahrenheit would change
sides. This was with all burners in service. After an outage on the
unit, during which time air register travel was adjusted and considerable
other boiler work was done, the situation cleared up. 3. The plant operations people were seeing
things for which they had no explanation and in some cases were happier
not knowing.
Of the three B&W gas fired boilers
operating with high temperature probes, two are of the El Paso design
and both have four probes each, the one Carolina design is a universal
pressure unit and has four probes installed. Installation into the boiler is difficult
and must be done properly or breakage will occur. Excluding breakage,
the probe life is in excess of one year each. Maintenance consists of
assuring that -- small amount clean, dry reference air is flowing to
the cell. We presently use high temperature probes,
on automatic control, on two B&W boilers. The 02 control is performing
quite well and controls the 02 to the ramped set point from 3 % at low
load to 0. 4 % at high load. The band width of 02 on the chart is approximately
0. 15 % 02. the much faster response and the location of the
probes makes a much tighter control loop than we have experienced before.
In the beginning, considerable effort was placed into designing a system to facilitate on-line probe replacement. The design utilized
an aspirating air mechanism to contain hot cases required by our pressurized
furnaces. Although this system functioned properly, safety hazards became
a major concern. Handling a probe from at least 1200'F furnace gas temperature
was the major concern. In addition, the installation of a new probe
requires careful insertion at a slow rate to prevent breakage. It was
decided to abandon the idea since the probes have an 18-24 month life
and are routinely replaced during an outage. CONCLUSION The high temperature 02 probes have proven
a valuable tool as a faster response than the back pass measurement.
Measuring 02 in the furnace area allows for burner and air register
adjustment which up to now has been a guess at best. In conjunction
with a good CO measurement, it is a tool for evaluating burner performance.
When the high temperature 02 probes are used in conjunction with economizer
outlet measurement of 02, the difference is a measurement of in-leakage
or tramp air. There is still more work to be done to obtain the best
performance from these probes. With the environmental requirements and
the probability of reduced O2 firing, this should become a vital measurement.
ACKNOWLEDGMENT 1. The Nernst equation was taken from
the user's manual for oxygen sensors from AACC/Zircoa, Solon Ohio.
|